STOVE INSTALLATION (CONT.) - For Qualified Installers Only! PAGE 13
Horizontal Vent Termination Requirements (see the illustration below)
A Minimum 9" (225 mm) clearance from any door or window
B Minimum 12" (300 mm) above any grade, veranda, porch, deck or balcony
C Minimum 12" (300 mm) from outside corner walls
D Minimum 12" (300 mm) from inside corner walls
E Minimum 11" (275 mm) clearance below unventilated soffits or roof surfaces
Minimum 18" (450 mm) clearance below ventilated soffits
Minimum 6" (150 mm) clearance from roof eaves
NOTE: Vinyl surfaces require 24" (600 mm)
11Ó Min.
6Ó Min.
Roof
Surface
Roof
Eaves
F Minimum 18" (450 mm) clearance below a veranda, porch, deck or balcony (must have two open sides)
G Minimum 48" (1220 mm) clearance from any adjacent building
H Minimum 84" (2130 mm) clearance above any grade when adjacent to public walkways or driveways
NOTE: may not be used over a walkway or driveway shared by an adjacent building
I Minimum 48" (1220 mm) clearance from any mechanical air supply inlet, 72" (1820 mm) for Canada
J Minimum 36" (910 mm) clearance above and 48" (1220 mm) below and to the sides of non-mechanical air supply inlet
K Minimum 36" (910 mm) from the area above the meter/regulator (vent outlet)
L Minimum 36" (910 mm) from the meter/regulator (vent outlet)
C
B
H
E
G
A
D
F
L
K
J
I
NOTE: Measure clearances to the nearest edge of the exhaust hood.
A
E
¥ Use the vinyl siding standoff (#950) when installing on an exterior with vinyl siding.
¥ Vent termination must not be located where it will become plugged by snow or other material
¥ These clearances meet UMC-1994 and the CNA/CGA-B149 code standards
Vertical Vent Termination Requirements (see the illustration below)
Roof Pitch
Flat to 6/12
6/12 to 8/12
8/12 to 9/12
9/12 to 10/12
10/12 to 11/12
11/12 to 12/12
12/12 to 14/12
14/12 to 16/12
16/12 to 18/12
18/12 to 20/12
20/12 or greater
Minimum Height*
1' (.3 M)*
1.5' (.45 M)*
2' (.6 M)
2.5' (.75 M)
3.25' (1 M)
4' (1.2 M)
5' (1.5 M
6' (1.8 M)
7' (2.15 M)
7.5' (2.25 M)
8' (2.45 M)
* In Canada the
vent termination
must be a
minimum 2' (.6 M)
tall and 2' (.6 M)
above any portion
of the roof within
10' (3 M) of the
vent.
Use the
chart to the
right to
determine
the required
vent
termination
height.
Height
Roof
Pitch
Use the vertical
termination (Part #991)
Electrical Connection
¥ Plug the power cord into a grounded 120 Volt outlet (do not remove the grounding plug).